Release 0 34-ST-25-20 MC Toolkit User Manual 83
7/03
Reference Data
Table 31 Glossary
Item Definition Description
Conformity
Response form of
sensor.
User selection of PV conversion algorithm: Linear or Square Root
D/A Trim Digital to Analog
Trim
Adjustment to digital-to analog (output) conversion algorithm that
aligns minimum and maximum values of scaled digital range to
minimum (0%) and maximum (100%) values of analog output.
Damping Digital algorithm in transmitter MPU that reduces noise in a PV that
is generated in the process or induced in transmitter components.
EU Engineering
Units
A standard scale of values, selected by the user from a standard set for
convenient display and interpretation.
Input 1. Physical property (e.g., pressure) applied to a sensor
2. Digital value, calculated in the transmitter, that represents
magnitude of the physical input
Local Meter A device associated with a single transmitter and installed locally (in
the transmitter housing) or remotely (in a separate housing) that
displays variables sensed or calculated in the transmitter.
Loop Test
(In Analog Mode only) a set of commands from the HHC that causes
the transmitter to provide 0% (4 mA) and 100% (20 mA) for testing
proper operation of all components of the current loop.
LRL Lower Range
Limit
Minimum value in the useful range of the physical property of a
transmitter at which a sensor can operate.
LRV Lower Range
Value
Minimum value in a continuous range of "normal" process values.
Meter Units User-selected scale of values that provides for convenient
interpretation of values in the associated transmitter.
Output Analog or digital value, calculated from the input, that is transferred
from the transmitter to a receiver (e.g., process control equipment)
PV Process Variable Measured magnitude of a primary physical property such as pressure
or temperature.
PV Input Physical property such as pressure or temperature, applied to an input
sensor
PV Units Process Variable
Units
Standard scale of values of a PV, selected by the user for convenient
display and interpretation.
Sensor Type Standardized designation of the physical design property of a sensor
(e.g., DP, AP for pressure TC, RTD for temperature.)