Procedural Considerations
Page 68 34-ST-25-20 MC Toolkit User Manual Release 0
7/03
Table 22 HART Calibration - Loop Test (non-Honeywell Transmitters)
HART Loop Test (non-Honeywell Transmitters)
Loop Test
This function verifies the
integrity of the physical
components of analog output
loop current in a process
application
To observe output current
levels, connect a voltmeter or
current meter into the current
loop.
Select the desired current
level, then select
Set Output.
Observe the meter, and select
Yes in the popup message to
command the transmitter to
go to the selected current
level.
To return to the input-
dependent current level,
select
Clear Output; this
popup message appears.
If the Back button is selected
before using the
Clear
Output command, the
message at right appears.
To go back to the
Calibration Menu, select
OK
in the popup, select the Clear
Output button, then select the
Back button.