Messages and Diagnostic Codes
Page 76 34-ST-25-20 MC Toolkit User Manual Release 0
7/03
Table 26 HART Messages
HART MESSAGES
Bad Manufacturer Code MC Toolkit does not recognize the manufacturer code from the
transmitter.
Bad Status code from the transmitter MC Toolkit does not recognize the status code from the
transmitter.
Bad Start character on HART Message! First byte in HART response message is not a valid byte(valid
bytes:0x02,0x82,0x06,0x86,0x01,0x81)
Device specific command error Possible error codes 6, 8, 9, 10, 11, 12, 13, 14 and 15.
Subset of these is defined for commands. If any value other than
these subset values, this message is displayed.
Error code 02: Invalid Selection The selection is not valid.
Error code 03:Passed parameter too large Entered value is too large.
Error code 04:Passed parameter too small Entered value is too small.
Error code 05:Too few data bytes received Internal error. Repeat command.
Error code 06:Wrong Password! The password entered is incorrect.
Error code 07:In Write Protect Mode The transmitter is in Write Protect Mode.
Error Code 08:Set to Nearest Possible Value Set to Nearest Possible Value
Error Code 09:Applied process too high Applied process too high or out of range.
Error code 09:LRV too high LRV is too high or out of range.
Error Code 09:Not in Proper Current Mode Not in Proper Current Mode
Error Code 10:Applied process too low Applied process too low or out of range.
Error code 10:LRV too low LRV too low or out of range.
Error Code 11:Excess correction attempted Attempted correction value is out of range.
Error Code 11:Invalid Transmitter variable Selected variable is invalid for this transmitter.
Error Code 11:Transmitter in Multidrop Mode!
Action could not be completed because the transmitter is in
multidrop mode.
Error code 11:URV too high URV too high or out of range.
Error Code 12:Invalid Units Invalid Units
Error code 12:URV too low URV too low or out of range.
Error code 13:Parameter out of limits Parameter is out of the valid range.
Error code 14:Span Too Small Span Too Small
Error Code 14:Warning:New LRV pushed URV
over Sensor Limit
The new URV has caused the URV to go over the sensor limits.
Error code 16:Access restricted Access to the parameter is not allowed.
Error code 32:Device is Busy! Device is currently busy; try command again.
Error Code 64: Command not implemented in
the Transmitter!
Action is not supported by the transmitter.