Compaq HSG80 - StorageWorks RAID Array Controller Specifikace Strana 58

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 296
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 57
2–30 Compaq StorageWorks HSG80 Array Controller ACS Version 8.5 Maintenance and Service Guide
12. Disconnect the PC or terminal from the controller maintenance port.
Replacing a Cache Module in a Dual-Redundant Controller
Configuration
Use the following steps in “Removing a Cache Module in a Dual-Redundant Controller
Configuration” and “Installing a Cache Module in a Dual-Redundant Controller
Configuration” to replace a cache module.
NOTE: The new cache module
must
contain the same memory configuration as the cache
module being replaced.
Removing a Cache Module in a Dual-Redundant Controller
Configuration
Use the following steps to remove a cache module:
1. Connect a PC or terminal to the maintenance port of the operational controller.
The controller connected to becomes “this controller;” the controller for the cache
module being removed becomes the “other controller.”
2. Disable failover and take the controllers out of their dual-redundant configuration with
the following command:
SET NOFAILOVER
3. Start FRUTIL with the following command:
RUN FRUTIL
The following display appears:
Do you intend to replace this controller’s cache battery? Y/N
4. Enter N(o). The following menu appears:
FRUTIL Main Menu:
1. Replace or remove a controller or cache module
2. Install a controller or cache module
3. Replace a PVA module
4. Replace an I/O module
5. Exit
Enter choice: 1, 2, 3, 4, or 5 ->
Zobrazit stránku 57
1 2 ... 53 54 55 56 57 58 59 60 61 62 63 ... 295 296

Komentáře k této Příručce

Žádné komentáře