13
For more information, visit www.hp.com/products/rackoptions
For more information on racks, visit www.hp.com/products/racks
RS-232/DB9; includes HP power-management software; more options available (see “UPS options”)
3-year HP warranty and integrated Care Pack Support with no additional costs
5
Part number
3
Part number for
HP AlphaServer,
Integrity, 9000
4
Form factor
Power output
(Watts)
Backup time at 75%
load
1
Load segments
Output (high-
voltage model)
Hot-swap batteries
Hot-swap
electronic modules
Shipping weight (kg)
Optional ERMs
ERM part number
for ProLiant
ERM part number
for AlphaServer,
Integrity, HP 9000
Communication
Warranty
Model R1500 XR, Intl R3000 XR R5500 XR, Intl R6000i R12000 XR
204404-B31
N/A
2U
1340W
7 mins
2
3
6x IEC 320 C13
Yes
Yes
48
2
218971-B21
N/A
192186-B31
(detached cord),
192186-B32
(IEC 309),
192186-
B33 (SCHUKO
plug), 192186-AR1
(South Africa plug)
J4367A
2U
2700W
7 mins
2
3
1x IEC 320 C19
(16A); 9x IEC 320
C13 (10A)
Yes
Yes
48
1
192188-B21
J4368A
326529-B31
N/A
3U
5400W
10 mins
2
2
4x IEC 320 C19;
4x IEC 320 C13;
1x IEC 309 (32A)
Yes
Yes
91
2
326564-B21
N/A
N/A
J4370A
6U
6000W
10 mins
2
5
3x IEC 320 C19
(16A); 12x IEC 320
C13 (10A)
No
Yes
136
2
347224-B21
J4371A
207552-B22
J4373A
10U
12000W
9 mins
2
See note 5
Hardwire; delivered
with 40A PDU
Yes
Yes
236
2
217800-B21
J4375A
Rack-mount UPS models
1
Backup times are estimated for typical applications at recommended load level of 75%. Actual performance will depend on
environment conditions, ambient temperature, battery age and other factors.
2
Increased system uptime possible with optional Extended Runtime Modules (ERMs).
3
Delivered with HP Rack and Power Manager and HP Power Manager UPS software, and rail kit for HP 10000 series racks.
4
Delivered with LanSafe UPS software and rail kits for HP/E racks.
5
Server Care Pack also supports UPS.
Komentáře k této Příručce