QuickSpecs
Compaq AlphaServer ES45
DA-10994 World Wide — Version 20 — June 27, 2002 30
Technical Specifications
Cabinet Configuration
H9A10 M-Series H9A15 M-Series
Dimensions (H x W x D)
(Depth includes rear door
extender)
67x 23.6 x 41.5 in/
170 x 60 x 105.4 cm
79 x 23.6 x 41.5 in/
200 x 60 x 105.4 cm
Shipping Dimensions
73 x 36 x 48 in/
185.5 x 91.5 x 122 cm
85 x 36 x 48 in/
216 x 91.5 x 122 cm
Weight
Configuration dependent Configuration dependent
Shipping Weight
Nominal: 946 lb/430 kg
Maximum: 1,375 lb/625 kg
Nominal: 1,056 lb/550 kg
Maximum: 1,408 lb/640 kg
System Unit
ENVIRONMENTAL
Temperature
Operating
(Tower, Pedestal, Rackmount)
50° to 95° F/10° to 35° C
Non-operating
-40° to 151° F/–40° to 66° C
Storage (60 days)
-40° to 151° F/–40° to 66° C
Rate of change
20° F/hr/11° C/hr
NOTE: Maximum operating temperature at sea level; reduce by 1.8° F (1° C) for
each 2,000 ft (600 m) above sea level.
Humidity
Operating 20% to 80%
Non-operating 20% to 80%
Storage (60 days) 10% to 95%
Rate of change 20% hr
Operating
82° F/28° C
Maximum Wet Bulb
Temperature
Storage (60 days)
115° F/46° C
Maximum Dew Point
Temperature
Operating
36° F/2° C
Heat Dissipation Nominal Maximum
Tower and Rack
980 W, 3347 BTU/hr 1440 W, 4918 BTU/hr
Pedestal
1560 W, 5328 BTU/hr 2400 W, 8196 BTU/hr
H9A10/H9A15 Cabinets
Configuration
dependent
4800 W, 16392 BTU/hr
Air Flow and Quality
Intake location Front
Exhaust location Rear Tower, Pedestal, Rack; Rear/top
H9A10/H9A15
Particle size N/A
Concentration N/A
Operating 10,000 ft/3,048 m
Altitude
(unpressurized)
Non-operating 40,000 ft/12,192 m
NOTE: Maximum operating temperature at sea level; reduce by 1.8° F (1° C) for
each 2,000 ft (600 m) above sea level.